BE1-87G
Power-Supply Options
Page 1-5
Wide-range, isolated, low-burden, switching
Input power (source voltage) is NOT polarity sensitive
Type
Input Voltage
Burden
(Nominal)
Nominal
Range
K (midrange)
48 Vdc
24 to 150 Vdc
3.8 W
J (midrange)
125 Vdc
25 to 150 Vdc
4.0 W
120 Vac
90 to 132 Vac
17.1 VA
L (low range)
24 Vdc
12 to 32 Vdc*
3.9 W
Y (midrange)
48 Vdc
24 to 150 Vdc
3.8 W
125 Vdc
25 to 150 Vdc
4.0 W
Z (high range
250 Vdc
68 to 280 Vdc
4.1 W
240 Vac
90 to 270 Vac
28.4 VA
*Type L begins operation at 14 Vdc;
Once operating, voltage can be reduced to 12 Vdc