Testing Differential:
Method 2
Set selector switch to D
Apply 1.0 amps to terminals 9-8 at 180
0
Apply 1.0 amps to terminals 6-8 at 0
0
and
ramp up
Relay should pick up at around 1.4 amps
a difference of 0.4 amps
Emulates current flow through generator
increasing on neutral side and not on
terminal side